3-2 Wiring
External 16 Module I/O Racks: Dimensions & Specifications
PS-5001
PS-5101
PS-5004
PS-5104
End View
Standard 16 Rack: PS-4100-11-216
Analog 16 Rack: PS-4100-11-316-A (for “-A” Option Only)
Notes:
•A Standard module is required for each Input or
Output used. See Appendix for module specs.
AC and DC modules can be mixed as needed.
Input modules can be used only with 5004 and 5104
units.
Output modules act like switches; they do not
supply power to loads.
Position 16 of Analog racks is dedicated to analog
output and will not work with other modules. If an
analog module is used, it must be installed in
position 16.
Odd Terminals: (+) or hot
Even Terminals: (-) or load
Slimline M16 Rack
Foot Mount Rack: PS-4100-11-M16-F
DIN Rail Rack: PS-4100-11-M16-D
Foot Mount (-F)
End Views
DIN Rail (-D)
Notes:
•A Slimline module is required for each Input or Output used.
See Appendix for module specs.
AC and DC modules can be mixed as needed.
Input modules can be used only with 5004 and 5104 units.
Output modules act like switches; they do not supply
power to loads.
Analog modules may be installed in position 16 only.
Module Fuses: 4 Amp, #PS-9005-0004
(Wickman 19370-K)
“A” Terminals: (-) or load
“B” Terminals: (+) or hot