4-1 Programming, Standard Features
Levels of Programming Access
The 5000 Series of controls have three levels of programming
access. Entry into these levels of programming is
accomplished through dedicated hardware inputs and/or
programmable enable codes entered through the keyboard.
Master Level—Accesses all programmable features. In
addition to all setpoints and functions, the Master Level also
establishes the keyboard entry codes for the “Setup” and
“Operator” access levels. Master Level programming also
determines which outputs are accessible to the operator.
NOTE: On units prior to date code 9740, operator access
was limited to setpoints and timed output values, unless
equipped with the Expanded Operator Access (-E) option.
Setup Level—Accesses all output setpoints and the
functions listed on the keyboard. These are control aspects
that may need occasional adjustment, but go beyond normal
operator responsibilities.
Operator Level—Functions available as specified in Master
Level programming. The operator is allowed to change the
following settings for output channels designated in FCN 6:
• Setpoints • Offset
• Timeouts • Active Program Number
• Motion Detection Settings • Speed Comp Settings
Master Programming is enabled when terminal 6 is connected
to terminal 1 or 2. The Master Level can only be accessed by
energizing this input.
Hardware Program Enable Circuits
Logic Terminal Strip
Operator Programming is enabled when terminal 9 is connected
to terminal 1 or 2. The Operator Level can also be accessed
through a keyboard enable code.
Keyboard Enable Codes for Setup and Operator Access
Programming Access Levels
LOGIC COMMON
PROGRAM SELECT 2
PROGRAM SELECT 3
MASTER PROGRAM ENABLE
OPERATOR PROGRAM ENABLE
MOTION DETECTION OUTPUT
OUTPUT GROUP ENABLE 1
+12VDC OUT - 150 mA MAX
1
2
3
4
5
6
7
8
9
10
PROGRAM SELECT 1
FEATURE MASTER SET UP OPERATOR
Enable Method hardware code hardware / code
Output Set Points All All Selected
Output Time Out Values All All Selected
Motion Set Points Yes Yes Selected
Offset Yes Yes Selected
Active Program Yes Yes Selected
Speed Compensation Yes Yes Selected
Direction of Rotation Yes No No
Scale Factor Yes No No
Set Up Enable Code Yes No No
Operator Enable Code Yes No No
Time Base Selection Yes No No
Motion ANDed Outputs Yes No No
Select Operator Outputs Yes No No
Output Enable Modes Yes No No
OPTIONAL FEATURES:
Lead/Trail Speed Comp Yes No No
Communication Setup Yes No No
Analog Setup Yes Yes Selected
The table below details which functions and set points can
be changed at the three levels of programming access. It
also indicates if the programming access levels can be
accessed by hardware input and/or keyboard enable code.
Either the Setup or Operator programming levels can be accessed by
entering the corresponding program enable code through the keyboard.
These codes can be 1, 2, 3, or 4 digit numbers and are established
during Master Level programming.
To Enter a program enable code number press:
FCN 0 ENT 1st digit 2nd digit 3rd digit 4th digit ENT
The PE codE message will disappear when a valid enable code is
entered.
The level of access gained depends upon which code number is
entered.
Programming access will time-out approximately 5 minutes after the
last keystroke. To cancel access before the 5 minute time-out press:
FCN 0 ENT CLR/CLE ENT